Floyd L. Davidson wrote:
> However, if the cable is a long run, and particularly if there
> is exposure to power lines, if the ground potential is different
> at the two ends, or if there are any other sources of induced
> noise in the cable, this arrangement has the best effect:
>
> +-------+ +-------+
> | | >--------- tx wire/pair ---------> | |
> | EQUIP | <--------- rx wire/pair ---------< | EQUIP |
> | | ========= cable shield ========= | |
> +-------+ | | +-------+
> | | | |
> | | | |
> o------+ +------o
> | |
> ----- Earth ----- Earth
> --- Ground --- Ground
If you really do need to connect at both ends then you may need to consider
inserting some impedance in the screen connections at both ends (usually a
capacitor and resistor in parallel). The resistor is large enough to
prevent high current flows but needs to be small enough to provide an
effective electrostatic drain. The capacitor provides a low impedance at
higher frequencies.
--
********************************************************************
Paul E. Bennett ....................<email://peb@xxxxxxxxxxxxxxxxxx>
Forth based HIDECS Consultancy .....<http://www.amleth.demon.co.uk/>
Mob: +44 (0)7811-639972
Tel: +44 (0)1235-811095
Going Forth Safely ....EBA. http://www.electric-boat-association.org.uk/
********************************************************************
.
- Follow-Ups:
- Re: RS485 is bidirectional does it mean it is fullduplex?
- From: Floyd L. Davidson
- Re: RS485 is bidirectional does it mean it is fullduplex?
- References:
- RS485 is bidirectional does it mean it is fullduplex?
- From: Swizi
- Re: RS485 is bidirectional does it mean it is fullduplex?
- From: Floyd L. Davidson
- Re: RS485 is bidirectional does it mean it is fullduplex?
- From: Grant Edwards
- Re: RS485 is bidirectional does it mean it is fullduplex?
- From: kunil
- Re: RS485 is bidirectional does it mean it is fullduplex?
- From: Floyd L. Davidson
- RS485 is bidirectional does it mean it is fullduplex?
- Prev by Date: Re: RS485 is bidirectional does it mean it is fullduplex?
- Next by Date: Re: Convert 2 digit decimal to binary in 8051
- Previous by thread: Re: RS485 is bidirectional does it mean it is fullduplex?
- Next by thread: Re: RS485 is bidirectional does it mean it is fullduplex?
- Index(es):
Relevant Pages
|
Loading